Fluke 116/323 HVAC Combo Kit - Includes Multimeter and Clamp Meter
主要特性
Fluke 116 Digital Multimeter. Designed by Electricians. Engineered by Fluke.
- Built-in thermometer for HVAC applications
- Microamps to test flame sensors
- Low input impedance: helps prevent false readings due to ghost voltage
- Large white LED backlight to work in poorly lit areas
- Resistance, continuity, frequency and capacitance
- Min/Max/Average with elapsed time to record signal fluctuations
- Compact ergonomic design for one-handed operation
- Compatible with optional magnetic hanger (ToolPak?)
- CAT III 600 V safety rated
Fluke 323 True-rms Clamp Meter. Rugged. Reliable. Precise.
- 400 A AC current measurement
- 600 VAC and DC voltage measurement
- True RMS AC voltage and current for accurate measurements on non-linear signals
- Resistance measurement up to 40 kΩ with continuity detection
- Slim, ergonomic design
- CAT IV 300 V/CAT III 600 V safety rating
產(chǎn)品概述: Fluke 116/323 HVAC Combo Kit - Includes Multimeter and Clamp Meter
Having the right tool for the job is essential. Having all the right tools when you need them is even better. The Fluke 116/323 HVAC Combo Kit gives you the best in a versatile, rugged multimeter and a fast-acting, general purpose clamp meter.
The Fluke 116 comes with the Fluke 80BK-A integrated DMM temperature probe; no need to carry a separate thermometer. The microamp function allows flame sensor measurement down to 0.1 microamps. The AutoV/LoZ function prevents false readings caused by ghost voltage. The Fluke 116 also has a large white LED backlight for work in poorly lit areas. It measures resistance, continuity, frequency, and capacitance and provides Min/Max/Average readings with elapsed time to record signal fluctuations.
Fluke 116 multimeters are independently tested for safe use in CAT III 600 V environments.
True RMS measurements and optimized ergonomics make the Fluke 323 True RMS Clamp Meter the best general purpose clamp meter for commercial and residential electricians. The Fluke 323 model is ideally suited for current measurements up to 400 A in tight cable compartments.
Together, the Fluke 116 HVAC Multimeter and 323 True RMS Clamp Meter give electricians the right tools for the job.
產(chǎn)品規(guī)格: Fluke 116/323 HVAC Combo Kit - Includes Multimeter and Clamp Meter
Fluke 116 HVAC Multimeter with Temperature and Microamps
Specifications | ||
Maximum voltage between any terminal and earth ground | 600 V | |
Surge protection | 6 kV peak per IEC 61010-1 600 V CAT III, Pollution Degree 2 | |
Display | 6,000 counts, updates 4 per second | |
Bar graph | 33 segments, updates 32 per second | |
Operating temperature | -10°C to +50°C | |
Storage temperature | -40°C to +60°C | |
Battery type | 9 volt Alkaline, NEDA 1604A/ IEC 6LR61 | |
Battery life | 400 hours typical, without backlight | |
Accuracy Specifications | ||
DC millivolts | Range/Resolution | 600.0 mV / 0.1 mV |
Accuracy | ±([% of reading] + [counts]): 0.5% + 2 | |
DC volts | Range/Resolution | 6.000 V / 0.001 V 60.00 V / 0.01 V 600.00 V / 0.1 V |
Accuracy | ±([% of reading] + [counts]): 0.5% + 2 | |
Auto volts | Range/Resolution | 600.0 V / 0.1 V |
Accuracy | 2.0% + 3 (DC, 45 Hz to 500 Hz) 4.0% + 3 (500 Hz to 1 kHz) | |
AC millivolts1 True RMS | Range/Resolution | 600.0 mV / 0.1 mV |
Accuracy | 1.0% + 3 (DC, 45 Hz to 500 Hz) 2.0% + 3 (500 Hz to 1 kHz) | |
AC volts1 True RMS | Range/Resolution | 6.000 V / 0.001 V 60.00 V / 0.01 V 600.0 V / 0.1 V |
Accuracy | 1.0% + 3 (DC, 45 Hz to 500 Hz) 2.0% + 3 (500 Hz to 1 kHz) | |
Continuity | Range/Resolution | 600 Ω / 1 Ω |
Accuracy | Beeper on < 20 Ω, off > 250 Ω; detects opens or shorts of 500 μs or longer. | |
Ohms | Range/Resolution | 600.0 Ω / 0.1 Ω 6.000 kΩ / 0.001 kΩ 60.00 kΩ / 0.01 kΩ 600.0 kΩ / 0.1 kΩ 6.000 MΩ / 0.001 MΩ |
Accuracy | 0.9% + 1 | |
Range/Resolution | 40.00 MΩ / 0.01 MΩ | |
Accuracy | 1.5% + 2 | |
Diode test | Range/Resolution | 2.000 V / 0.001 V |
Accuracy | 0.9% + 2 | |
Capacitance | Range/Resolution | 1000 nF / 1 nF 10.00 μF / 0.01 μF 100.0 μF / 0.1 μF 9999 μF / 1 μF 100 μF to 1000 μF |
Accuracy | 1.9% + 2 | |
Range/Resolution | > 1000 μF | |
Accuracy | 5% + 20% | |
LoZ capacitance | Range | 1 nF to 500 μF |
Accuracy | 10% + 2 typical | |
Temperature2 (Type-K thermocouple) | Range/Resolution | -40°C to 400°C / 0.1°C |
Accuracy | 1% + 102 | |
Range/Resolution | -40°F to 752°F / 0.2°F | |
Accuracy | 1% + 182 | |
AC μamps True RMS (45 Hz to 500 Hz) | Range/Resolution | 600.0 μA / 0.1 μA |
Accuracy | 1.0% + 2 | |
DC μamps | Range/Resolution | 600.0 μA / 0.1 μA |
Accuracy | 1.0% + 2 | |
Hz (V or A input)2 | Range/Resolution | 99.99 Hz / 0.01 Hz 999.99 Hz / 0.1 Hz 9.999 Hz / 0.001 Hz 50.00 Hz / 0.01 Hz |
Accuracy | 0.1% + 2 | |
1. All AC voltage ranges except Auto-V/LoZ are specified from 1% to 100% of range. Auto-V/LoZ is specified from 0.0 V. 2. Temperature uncertainty (accuracy) does not include the error of the thermocouple probe. ? Frequency is AC coupled, 5 Hz to 50 kHz for AC voltage. Frequency is DC coupled, 45 Hz to 5 kHz for AC current. ? Temperature Range/Resolution: -40°F to 752°F / 0.2°F | ||
Mechanical and General Specifications | ||
Size | 167 x 84 x 46 mm (6.57 x 3.31 x 1.82 in) | |
Weight | 550 g | |
Warranty | 3 years |
Fluke 323 True-rms Clamp Meter
Specifications | ||
AC current | Range | 400.0 A |
Accuracy | 2% ±5 digits (45 Hz to 65 Hz) 2.5% ±5 digits (65 Hz to 400 Hz) | |
AC voltage | Range | 600.0 V |
Accuracy | 1.5% ±5 digits | |
DC voltage | Range | 600.0 V |
Accuracy | 1.0% ±5 digits | |
Resistance | Range/Resolution | 400.0 Ω/ 4000 Ω |
Accuracy | 1.0% ±5 digits | |
Continuity | ≤ 70 Ω | |
AC response | True-rms | |
Data hold | Yes | |
Size | H x W x D (mm) | 207 x 75 x 34 |
Max wire diameter | 30 mm (600 MCM) | |
Weight | 265 g | |
Category rating | CAT III 600 V CAT IV 300 V | |
Warranty | Two-year |
型號: Fluke 116/323 HVAC Combo Kit - Includes Multimeter and Clamp Meter
Includes Multimeter and Clamp Meter
手冊 + 資源: Fluke 116/323 HVAC Combo Kit - Includes Multimeter and Clamp Meter
- 116 | 用戶手冊
- 323/324/325 | 用戶手冊
- 110/113/114/115/116/117 | 安全須知
- 114, 115, 116, and 117 | 校準(zhǔn)手冊
- 117, 116,115,114,113 and 110 Plus | 內(nèi)存易失性聲明
- 302+/303/305/323/324/325 | 內(nèi)存易失性聲明
- 323/324/325 | 快速參考指南
- 323/324/325 | 安全須知
- 323/324/325 | 安全數(shù)據(jù)表補遺
- 323/324/325 | 校準(zhǔn)手冊
- 323/324/325 | 校準(zhǔn)手冊補遺
- Fluke 116 True-rms Multimeter | 快速參考指南